General Specification
Main Control function Modulation models Optimized space voltage vector SVPWM modula-tion
Control models Space voltage vector SVPWM control(Optimized compensation characteristic in low frequency dead zone)
Frequency definition Digital Setting: ×±0. 01% highest frequency;
Analog Setup: ×±0.2% highest frequency
Frequency accuracy Digital Setting:0.01Hz;
Analog Setup:×0.1% highest frequency
Start frequency
0.40Hz~20.00Hz
Torque boost Auto torque boost,manual torque boost 0.1%~30.0%
V/FFFFF curve Two modes:linear Acc/Dec, S ramp Acc/Dec;seven kinds of Acc/Dec time (Maximum:6000 minutes) and unit(minute or second) is selectable.
Acc/Dec curve
Two modes:linear Acc/Dec, S ramp Acc/Dec;seven kinds of Acc/Dec time (Maximum:6000 minutes) and unit(minute or second) is selectable.
DC injection braking Initial frequency of DC injection braking process:0~15.00Hz
Braking time:0~60.0 s
Braking current:0~80%
Dynamic braking
Internal dynamic braking, can be connected with external braking resistor
Jog
Range of jog frequendy:0.1Hz~50.00Hz, Acc/Dec time of jog operation 0.1~60.0s
Internal PI
Be able to form close loop control system easily
Multi-step
speed running
Multi-step speed running can be realized by internal PLC or control terminals
Traverse operation
Traverse operation with adjustable central frequency
Auto voltage regulation
(AVR)
When souce voltage changes, the modulationg rate can be adjusted automatically,so the output voltage is unchanged
Auto energy saving operation V/F curve is optimized automatically according to the load condition to realize energy saving operation
Auto current limiting
Operating current is limited automatically to avoid frequent tripping of the drive
Fix-length control
The driver stops when preset fixed length is reached
Communication
function
With master-slave multimachine linkage function and standard RS485 port, support communication protocol with Modbus-RTU form
Operating function
Methods of inputting operating commands
Operation panel setup;control terminals setup;serial port setup;three modes can be selected.
Methods of setting up frequency Keyboard analog potentiometer setup;
keys setup;function code digital setup; serial port setup;terminal UP/DOW setup;analog voltage setup;analog current setup; pulse setup;combination setup; different setting modes are selectable
Digital value input channel
Forward/ Reverse command;6 digital value input,can be set for 35 kinds of function,X6 support 0~20KHz pulse output
Analog input channel
2 analog input ,4~20mA and 0~10V can be selected
Analog output channel
1 analog output, 0~10V, can set output of reference frequency, output frequency and so on
Digital, vaule output channel
1 Bi-direction open-collector output terminal;1 relay output signal;1 pulse output signal (0~20KHz) can realize several ouput signal
Operation panel
LED Digital Display
Can display setup frequency, output voltage, output current and other parameters.
External Instrument Display
Display output frequency, output current, output voltage and other physical quantity
Key Lock
Lock all the keys
Parameter Copy
Function code parameter copy among inverters can be realized bye remote keyboard
Protection Function
Over current protection;over voltage protection;under voltage protection;over heat protection;over load protection
Optional parts